67
1
5.6.2.3 Access from the display
/ Ekip Com Profibus DB -module
With modules connected and energized,
the presence of the modules on the mod-
ule slot activates additional menus on
the display.
The following table illustrates the path for
accessing the configuration parameters
of the modules from the display:
Settings (*Default value)
Description
:
Modules (Optional modules)
Ekip Com Profibus DB
Serial address
1…125, default 125*
Address to be assigned to the modules.
IMPORTANT: devices connected to the same
network must have different addresses
:
—
Table 5.10 Configuration of Ekip Com Profibus DB -module in HMI
The following table illustrates the path
from the display for accessing informa-
tion on the module:
About
Description
:
Modules (Optional modules)
Ekip Com Profibus DB -module
SN
Serial number
Version
Software version
:
—
Table 5.11 Information of Ekip Com Profibus DB -module in HMI
L
CD
, T
O
U
CH
Содержание Zenith ZTG 30
Страница 2: ......
Страница 6: ...6 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE 1 ...
Страница 10: ...10 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE 1 ...
Страница 52: ...52 1 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...
Страница 91: ...91 1 Fig 7 3 ZTGD delayed transition circuit diagram ...
Страница 93: ...93 1 Figure A Figure B ...
Страница 94: ...94 1 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE Figure C ...
Страница 96: ...2 96 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...
Страница 108: ...2 108 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...
Страница 114: ...2 114 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...