39
3 4ZBT S _ 3 0 -1 2 0 0A rev. A / 1 S CC 3 0 3 0 4 3 M 0 2 01
1
NOTE!
In Test location all electrical opera-
tions are allowed. The switch can be oper-
ated I-O-II.
6
When rack out the ATS to Isolated
location, the switch must be in OFF-
position. Now follow the steps 3 to 5.
When button returns, it is a sign that
next locations has been reached and
the location now is “Isolated”.
NOTE!
In Isolated location there is no
power available.
"Bypass System Overview" -page in HMI
of Bypass switch:
When ATS is drawn in/
out the list "
Connected - Test - Isolated"
(
all in grey) indicates a Location error be-
cause the IO-connection is disconnected
from the contacts at different times while
the switch is racked in/out. When the lo-
cations are reached the colours in the list
will change; when reached the Test loca-
tion, Test will be in yellow (
Test
), all the
other in grey and when the Isolation loca-
tion is reached, Isolation will be in orange
(
Isolated
) and all the other in grey, see Fig.
3.29.
While the ATS is racked out to the Test lo-
cation,
"Switch Overview " -page in HMI
of ATS
do not display the location status.
When the Test location is reached and the
"Racking in/out mechanism" button re-
turns to the normal position, the HMI dis-
play updates the latest location.
When the ATS is racked out to the Isolated
location, the plug-in connections are dis-
connected from the busbar and the
switch loses the power. In this case, all
connections (including I/O signals) are
disconnected, which also interrupts the
power supply to the HMI. In this case, the
HMI of the Bypass switch shows the sta-
tus of both switches on the “Bypass Sys-
tem Overviw” -page.
See the next two pages the Fig. 3.28 for
the use of the draw-out mechanism to
rack out the switch and Fig. 3.29 for sta-
tus of the switches on the HMIs of both
switches while racking out the ATS.
—
Fig. 3.27 Transferring to Isolation location, numbers refer
to the steps
3 5
6
Содержание Zenith ZBTS T Series
Страница 2: ...2 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Страница 6: ...6 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Страница 10: ...10 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Страница 44: ...44 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Страница 58: ...58 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Страница 68: ...68 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Страница 100: ...2 100 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 3 ...
Страница 103: ...2 103 34ZBTS _ 30 1200A rev A 1SCC303043M0201 4 ...
Страница 105: ...2 105 34ZBTS _ 30 1200A rev A 1SCC303043M0201 4 ...
Страница 107: ...2 107 34ZBTS _ 30 1200A rev A 1SCC303043M0201 4 ...
Страница 108: ...2 108 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 4 ...
Страница 109: ...2 109 34ZBTS _ 30 1200A rev A 1SCC303043M0201 4 ...