31
3 4ZBT S _ 3 0 -1 2 0 0A rev. A / 1 S CC 3 0 3 0 4 3 M 0 2 01
1
10:55
TruONE ATS
Bypass System Overview
Bypass Status
Connected
Test
Isolated
ATS Status
Connected
Test
Isolated
G
3.3.1.2 Bypass System Overview
—
Fig. 3.10 Last page shows Bypass System Overview
Draw-out Locations
• Connected
= Main and Control circuit
connected
• Test
= Main circuit isolated
• Isolated
= Main and Control circuit iso-
lated
• Connected - Test - Isolated
= Location
error; If another switch is moved in/out
or there is some failure in location sta-
tus
Basic information can be found in both
switches' own HMI, see Fig. 3.12:
1
Source Available
2
Switch position I-O-II
3
Switch location
4
Supply ok and connected to load
NOTE!
The LOAD led should be ON when
the switch is at
Connected
location and
on I or II-position. At
Test
location the
LOAD led should be OFF because the main
circuit of the switch is isolated.
AUTO
!
S1
S2
l
ll
O
LOAD
S1
S2
l
ll
O
LOAD
—
Fig. 3.11 Connected location and I-position: LED is ON,
Test location: LED is OFF
Lamp
test
l
ON
Off
load
test
ll
ON
Auto
Alarm reset
On
load
test
Bypass
time
delay
Dropout ΔU / Δf
Manual
retransfer
Generator
stop delay
4 min
30 s
ΔU 5% / Δf 5%
ΔU 10% / Δf 5%
ΔU 15% / Δf 10%
ΔU 20% / Δf 10%
0
1
2
3
4
5
10
15
20
30
S1 Failure
delay [s]
S1 Return
delay [min]
On
Off
Auto
config
Start
Ok
Priority
No priority
Source 1
In-phase
monitor
Off
On
AUTO
!
LOAD
l
ll
O
O Position
delay
4 s
0 s
O
OFF
S1
S2
Lamp
test
l
ON
Off
load
test
ll
ON
Auto
Alarm reset
On
load
test
Bypass
time
delay
Dropout ΔU / Δf
Manual
retransfer
Generator
stop delay
4 min
30 s
ΔU 5% / Δf 5%
ΔU 10% / Δf 5%
ΔU 15% / Δf 10%
ΔU 20% / Δf 10%
0
1
2
3
4
5
10
15
20
30
S1 Failure
delay [s]
S1 Return
delay [min]
On
Off
Auto
config
Start
Ok
Priority
No priority
Source 1
In-phase
monitor
Off
On
AUTO
!
S1
S2
LOAD
ll
O
O Position
delay
4 s
0 s
O
OFF
l
S1 Connected to Load
ATS Connected
Load Current
.... A
04:11
G
TruONE ATS
Switch Overview
S1 p
Ok Ok
S2
1
1
3
4
05:17
TruONE ATS
Bypass System Overview
G
Bypass Status
Connected
Test
Isolated
ATS Status
Connected
Test
Isolated
3
2
—
Fig. 3.12 Basic information can be found in both switches'
own HMI
NOTE!
Normally, the ATS is in the rack at
Connected
location and on the I-position,
it supplies the load. At the same time, the
Bypass switch is also at
Connected
loca-
tion, but it is on the O-position. Remark;
The fixed type Bypass is always consid-
ered to be at
Connected
location.
Содержание Zenith ZBTS T Series
Страница 2: ...2 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Страница 6: ...6 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Страница 10: ...10 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Страница 44: ...44 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Страница 58: ...58 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Страница 68: ...68 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Страница 100: ...2 100 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 3 ...
Страница 103: ...2 103 34ZBTS _ 30 1200A rev A 1SCC303043M0201 4 ...
Страница 105: ...2 105 34ZBTS _ 30 1200A rev A 1SCC303043M0201 4 ...
Страница 107: ...2 107 34ZBTS _ 30 1200A rev A 1SCC303043M0201 4 ...
Страница 108: ...2 108 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 4 ...
Страница 109: ...2 109 34ZBTS _ 30 1200A rev A 1SCC303043M0201 4 ...