Zenith ZBTS T-series 100-1200A, I N S TA LL ATI O N A N D O PER ATI N G I N S TR U C TI O N
1
Notice
A protective device such as a moulded case
circuit breaker or fused disconnect switch
MUST be installed on both sources of incom-
ing power for circuit protection and as a dis-
connection device.
The Bypass-Isolation Automatic Transfer
Switch consists of these main modules:
• The two automatic transfer switches:
- ATS is always draw-out version (lower
switch module)
- Bypass can be fixed or draw-out
version (upper switch module)
• Customer main connections, Source 1,
Source 2 and Load, on the top of the
cabin
• The Control Plate (bottom module)
- Customer connections: Generator
start/stop terminals
- Control circuit
- Place for optional accessories
• Racking in/out -mechanism
• Both switches have operation panel HMI
at the door
The modules containing the switch are
connected to the busbars located at the
rear of the modules and the entire pack-
age is mounted in an enclosure. The ATS
switch in the lower switch module is al-
ways a draw-out version that includes an
in/out rack for easy maintenance. The up-
per switch module, the Bypass switch, is
available in either a fixed or draw-out ver-
sion, but all the functions are exactly the
same both Bypass and ATS switches.
The top module of enclosure is for cable
lugs for Source 1, Source 2 and for Load.
The lugs are located behind transparent
covers. See the location of lugs in Fig. 2.6.
The Control Plate is located in the bottom
module equipped with own inside door.
The front side of the door is reserved for
the customer connections e.g. generator
start/stop terminals and also included an
empty space for the accessories. Back
side of the Control Plate door are all other
components which are necessary for the
control system.
The switch racking in/out mechanism is
on enclosure’s door also in the upper
switch module, when the Bypass switch is
draw-out version. The tool for the racking
in/out system is located in the mecha-
nism behind the transparent cover. The
default location is the lower switch mod-
ule, where ATS is always the draw-out
version.
Danger
Hazardous voltage. Turn OFF all power before
installation, adjustment, or removal of the
transfer switch or any of its components.
Warning
Due to hazardous voltage and current, ABB
recommends that ABB certified technician or
qualified electrician perform the installation
and maintenance.
Содержание Zenith ZBTS T Series
Страница 2: ...2 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Страница 6: ...6 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Страница 10: ...10 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Страница 44: ...44 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Страница 58: ...58 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Страница 68: ...68 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Страница 100: ...2 100 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 3 ...
Страница 103: ...2 103 34ZBTS _ 30 1200A rev A 1SCC303043M0201 4 ...
Страница 105: ...2 105 34ZBTS _ 30 1200A rev A 1SCC303043M0201 4 ...
Страница 107: ...2 107 34ZBTS _ 30 1200A rev A 1SCC303043M0201 4 ...
Страница 108: ...2 108 Zenith ZBTS T series 100 1200A INSTALL ATION AND OPER ATING INSTRUCTION 4 ...
Страница 109: ...2 109 34ZBTS _ 30 1200A rev A 1SCC303043M0201 4 ...