68
Tru O N E® AT S , I N S TA LL ATI O N A N D O PER ATI N G I N S TR U C TI O N
1
TO
U
C
H
Settings (continued)
*Default
Standard I/O settings (continued)
O 01 (continued)
Function (continued)
Pre-transfer Signal
Signal is activated and transfer is delayed
according to pre-transfer delay. Signal is kept
activated according to post-transfer delay after
transfer.
Source 1 available
No anomalies in S1 voltage supply.
Source 2 available
No anomalies in S2 voltage supply.
Load Shed 1
Used for shedding non-essential loads before
transferring to non-priority source. Signal is
activated before transferring to non-priority
source according to load shed delay and kept
activated until load is transferred back to
priority source.
Elevator pre-signal
Signal is activated and transfer is delayed
according to Elevator pre-signal delay. Signal is
kept activated according to Elevator post-signal
delay after transfer.
Contact
Type
NC
Active open.
NO*
Active closed.
Modules
See Chapter 5, Electronic accessories
System
RESET to Factory Setting
Restore default parameter values
Date
1)
Month day, year
Time
1)
Hours:Minutes
Language
English*
Italian
French
German
Spanish
Russian
Chinese
New Password
Five digits
Temperature Unit
Celsius*
Fahrenheit
Clock Format
24 h*
12 h
Continued on the next page
1)
RTC capacitor must be charged before inserting Date/Time. RTC capacitor is charged from source voltage (not AUX)
and takes about 10 minutes. RTC capacitor keeps the date/time saved for 48 h in case of no source voltage available.
Содержание TruONE ATS
Страница 2: ......
Страница 6: ...6 TruONE ATS INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Страница 151: ... Notes ...
Страница 152: ... Notes ...
Страница 153: ... Notes ...
Страница 154: ... Notes ...
Страница 155: ... Notes ...
Страница 156: ... Notes ...
Страница 157: ... Notes ...
Страница 159: ......