84
Tru O N E® AT S , I N S TA LL ATI O N A N D O PER ATI N G I N S TR U C TI O N
1
L
CD
, T
O
U
CH
5.6.1.3 Access from the display /
Ekip Com Modbus RTU –module
With modules energized the presence of
the modules on the module slot activates
additional menus on the display.
The following table illustrates the path for
accessing the configuration parameters
of the modules from the display:
Settings (*Default value)
Description
:
Modules (Optional modules)
Ekip Com Modbus RTU
Serial address
1… 247, default 247*
Address to be assigned to the modules.
NOTE: devices connected to the same network
must have different addresses
Baudrate
9600 bit/s, 19200 bit/s*,
38400 bit/s
Data transmission speed
Physical protocol
8.E,1*, 8.O,1, 8.N,2, 8.N,1
8.E,1 = 8 data bits, 1 EVEN parity bit, 1 STOP bit
8.O,1 = 8 data bits, 1 ODD parity bit, 1 STOP bit
8.N,2 = 8 data bits, no parity bit, 2 STOP bits
8.N,1 = 8 data bits, no parity bit, 1 STOP bit
:
—
Table 5.7 The path for accessing the configuration parameters of the Ekip Com Modbus RTU -module from the display
About
Description
:
Modules (Optional modules)
Ekip Com Modbus RTU
SN
Serial number
Version
Software version
:
—
Table 5.8 Information of Ekip Com Modbus RTU -module in HMI
The following table illustrates the path
from the display for accessing informa-
tion on the module:
Содержание TruONE ATS
Страница 2: ......
Страница 6: ...6 TruONE ATS INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Страница 151: ... Notes ...
Страница 152: ... Notes ...
Страница 153: ... Notes ...
Страница 154: ... Notes ...
Страница 155: ... Notes ...
Страница 156: ... Notes ...
Страница 157: ... Notes ...
Страница 159: ......