53
3 4 OX _ 3 0 -16 0 0 rev. B / 1 S CC 3 0 3 01 1 M 0 2 01
1
LC
D
Settings
*Default
Standard I/O Settings (continued)
O 01 (continued)
Function (continued)
Pre-transfer Signal
Signal is activated and transfer is delayed according
to pre-transfer delay. Signal is kept activated
according to post-transfer delay after transfer.
Source 1 Available
No anomalies in S1 voltage supply.
Source 2 Available
No anomalies in S2 voltage supply.
Load Shed 1
Used for shedding non-essential loads before
transferring to non-priority source. Signal is
activated before transferring to non-priority source
according to load shed delay and kept activated until
load is transferred back to priority source.
Elevator pre-signal
Signal is activated and transfer is delayed according
to Elevator pre-signal delay. Signal is kept activated
according to Elevator post-signal delay after
transfer.
Contact
type
NC
Active open.
NO*
Active closed.
Modules (See Chapter 5, Electronic accessories)
System
RESET to Factory Setting
Restore default parameter values.
Date
1)
Month day, year
Time
1)
Hours:Minutes
Language
English*
Italian
French
German
Spanish
Russian
Chinese
New Password
Five digits
Temperature Unit
Celsius*
Fahrenheit
Clock Format
24 h*
12 h
Display Contrast
10 - 100% (30 %*)
(continued)
1)
RTC capacitor must be charged before inserting Date/Time. RTC capacitor is charged from source voltage (not AUX)
and takes about 10 minutes. RTC capacitor keeps the date/time saved for 48 h in case of no source voltage available.
Содержание TruONE ATS
Страница 2: ......
Страница 6: ...6 TruONE ATS INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Страница 151: ... Notes ...
Страница 152: ... Notes ...
Страница 153: ... Notes ...
Страница 154: ... Notes ...
Страница 155: ... Notes ...
Страница 156: ... Notes ...
Страница 157: ... Notes ...
Страница 159: ......