5.6.2.2 Termination resistor
The Ekip Com Profibus DP modules pro-
vide the possibility to insert a 220 Ω ter
-
mination resistor on the RS-485 bus, by
setting the DIP-switches Rterm (1 and 2)
on the side of the modules, in position
ON.
In the event of termination of the bus, a
390 Ω pull-up or pull-down resistor must
also be inserted on the lines, by setting
the DIP-switches Rpol (3 and 4), in posi-
tion ON.
These options must be selected before in-
stallation of the modules.
—
Fig. 5.16 Termination resistor; To enable the Rterm,
the dip-switches 1 and 2 must be positioned to
ON. When Rterm is activated, the Rpol must also
be activated by turning dip-switches 3 and 4 to
ON-position. These options must be selected
before the installation of the modules
Rterm Rpol
220Ω
on
on
off
off
ON IA
1 2 3 4