8.2.4 Phase barriers
Phase barriers must be used between the
LOAD side terminals of TruONE automatic
transfers switches with switch types
OX_400U/500E…1200U/1600E. These
switch types include the phase barriers
for LOAD side from the factory. Additional
phase barriers to be used for the SOURCE
side terminals must be ordered separately
when needed.
—
8.3
Clearances per UL1008
C
B
A
C
D
—
Fig. 8.9 Mounting of phase barriers.
Fig. 8.10 UL standard switches, clearances per UL1008
Size (Current)
A [in /mm]
B [in /mm]
D [in /mm]
C
OX_30...200U_
1 / 26
0.5 / 13
0.5 / 13
According to the
OX_260...400U_
1 / 26
0.5 / 13
0.5 / 13
UL1008 standard
OX_600U_
1 / 26
0.5 / 13
0.5 / 13
OX_800U_ ...OX_1200U_
1 / 26
0.5 / 13
0.5 / 13
Minimum enclosure size or equivalent volume
Size (Current)
Width [in /mm]
Height [in /mm]
Depth [in /mm]
OX_30...200U_
23.6 / 600
31.5 / 800
11.8 / 300
OX_260...400U_
23.6 / 600
31.5 / 800
11.8 / 300
OX_600U_
23.6 / 600
31.5 / 800
11.8 / 300
OX_800U_ ...OX_1200U_
31.5 / 800
39.4 / 1000
11.8 / 300
A07
4
91
A07
4
8
9