38
Tru O N E® AT S , I N S TA LL ATI O N A N D O PER ATI N G I N S TR U C TI O N
1
1
Auto config: Automatically detecting
Source 1 and Source 2 parameters.
Automatic configuration sequence is
started by setting DIP to 'Start'
position. Parameter detection is
ready when AUTO LED flashes at 5 Hz.
After this the DIP must be set to 'Ok'
position to resume normal operation.
Check power supply of the voltage
source in case the Alarm LED keeps
flashing instead of AUTO LED. This
indicates that system parameters
cannot be detected from the supplied
voltage.
2
In-phase monitor:
On: Enable in-phase monitor
Off: Disable in-phase monitor
3 Priority:
No priority: Application 'Two
Transformers / No Priority' selected
Source 1: Application 'S1-Transformer
/ S2-Generator' selected.
Lamp
test
Off
load
test
Auto
Alarm reset
On
load
test
Bypass
time
delay
Dropout ΔU / Δf
Manual
retransfer
Generator
stop delay
4 min
30 s
ΔU 5% / Δf 5%
ΔU 10% / Δf 5%
ΔU 15% / Δf 10%
ΔU 20% / Δf 10%
0
1
2
3
4
5
10
15
20
30
S1 Failure
delay [s]
S1 Return
delay [min]
On
Off
Auto
config
Start
Ok
Priority
No priority
Source 1
In-phase
monitor
Off
On
AUTO
!
S1
S2
LOAD
l
ll
O
Center
/OFF
delay
4 s
0 s
1
6
2
3
4
7
9
8
AUTO
!
S1
S2
LOAD
l
ll
O
5
3.6.2 Configuration by DIP-switches
—
Fig. 3.9 DIP-switches for configuration in Level 2 HMI
A07
4
8
6
D
IP
Содержание TruONE ATS
Страница 2: ......
Страница 6: ...6 TruONE ATS INSTALL ATION AND OPER ATING INSTRUCTION 1 ...
Страница 151: ... Notes ...
Страница 152: ... Notes ...
Страница 153: ... Notes ...
Страница 154: ... Notes ...
Страница 155: ... Notes ...
Страница 156: ... Notes ...
Страница 157: ... Notes ...
Страница 159: ......