Tru O N E® AT S , I N S TA LL ATI O N A N D O PER ATI N G I N S TR U C TI O N
1
TO
U
C
H
Parameters (continued)
*Default
Device Parameters (continued)
Generator Exercisers
Switch and generator functioning can be tested
automatically and also periodically by using four
independent exerciser events. Test on load
function starts the generator and transfers the
load to it. Test off load function only starts the
generator for the duration of the event.
Overlapping events are prioritized, event 1 has the
highest priority.
Exerciser 1 / 2 / 3 / 4
Status
Disabled*
Non-periodic
Daily
Weekly
Bi-weekly
Monthly
Yearly
Function
No Function*
Test on Load
Test off load
Duration
(hh:mm:ss)
00:00:00...24:00:59 (00:01:00*)
Time
(hh:mm)
Starting time of the event.
00:00*...23:59
Date (month
day, year)
Starting date of the event
Jan 01, 2000... (---*)
Application
S1-Transformer/S2-Generator*
S2-Transformer/S1-Generator
2 Transformers/S1 Priority
2 Transformers/S2 Priority
2 Transformers/No Priority
Continued on the next page