101
Table 11.3.-3
Additional MMS services for SCL.2 and SCL.3
SCL conformance
Client-CR
Server-CR
Base
F/S
Value/Range
Base
F/S
SPA-ZC 402/
Comments
MMS Services
Not Supported
GetCapability-
List
O
i
o
i
Supported
GetDomainAt-
tributes
O
o
o
m
Not Supported
LoadDomain
O
a)
o
a)
Not Supported
StoreDomain
O
b)
o
b)
Not Supported
a)
Must be m if support SCL.3 is declared.
b)
Must be m if support for remote creation of a SCL is declared.
11.4.
SCL control block
The SCL control block must have a functional constraint of SC. This control block
must occur in LLN0 only.
The SCL control block must be a structured MMS type definition that contains the
ordered named components defined in Table 11.4.-1.
Table 11.4.-1
Definition of SCL control block
IEC 61850-8-
1Component
Name
MMS
TypeDescription
r/w
m/o
Comments
SPA-ZC 402/Comments
validate
VISIBLE-STRING
size of 64 octets
rw
mo
Must be m if support for
remote activation of an SCL
is declared.
N/A for TP client
valState
Unsigned Integer -
8 bits
r
m
(0) - NOT-VALIDATED
(1) - VALIDATION-ERROR
(2) - VALIDATED
(3) - VALIDATION-IN-
PROGRESS
(4) - NOT-SUPPORTED
(5) - VALIDATE-FILE-
PRESENT
N/A for TP client
activate
VISIBLE-STRING
size of 64 octets
rw
mo
Must be m if support for
remote activation of an SCL
is declared.
N/A for TP client
11.5.
Protocol implementation conformance statement
In the following tables basic protocol conformance statements (PICS) are defined.
11.5.1.
Profile conformance
SPA/ Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
SPA-ZC 402
SPA-ZC 402
1MRS755380
Содержание SPA-ZC 402
Страница 2: ......
Страница 6: ...6 ...
Страница 8: ...8 ...
Страница 12: ...12 ...
Страница 14: ...14 ...
Страница 28: ...28 ...
Страница 54: ...54 ...
Страница 58: ...58 ...
Страница 68: ...68 ...
Страница 104: ...104 ...
Страница 106: ...106 ...
Страница 108: ...108 ...
Страница 110: ...110 ...