37
groups, and functional constraint defines the data attributes. This is MMS protocol's
naming feature, which is the basic part of naming and protocol definition in the
IEC 61850 standard.
Delete the dataset by selecting the line and either pressing DELETE or selecting
Edit > Delete function
.
A040028
Fig. 6.5.-1
Dataset Editor
Dataset Editor columns:
*
IdInst
Instance of Logical Device to which referenced dataset belongs
*
Prefix
Freely configurable part of LN Caption
*
InInst
Instance of the LN type
Class of the LN type
*
InClass
*
doName
Name of the data object from which dataset is formed
*
daName
Name of the data attribute from which dataset is formed from
*
fc
Identifies the signal measurement type to MX, if the status is ST
Prefix, InClass and InInst define the object tree's caption. Caption is shown in the
following way: I InInst = LN Caption.