53
When the IEC 61850 client has been notified of the incoming record, the client
should read the COMTRADE files from SPA-ZC 402 by using FTP or IEC 61850
File Transfer connection. The client must remove the files after successful reading to
maintain free space for forthcoming records. The files are named as follows:
File name
Example
Description
yymmddnn.cfg
70010104.cfg
Configuration file
yymmddnn.dat
70010104.dat
Data file
yymmddnn.inf
70010104.inf
Information file
The filename consists of the following parts:
Part
Format
Description
yy
00
–
99
Record creation timestamp, year
mm
01
–
12
Record creation timestamp, month
dd
01
–
31
Record creation timestamp, date
nn
00 - 99
Running serial number of the records of the
same day. The Configuration, Data and
Information files related to one record have
the same serial number.