5. Install a new IED by right-clicking the IEC 61850 device and selecting
New >
Communication
. Select the appropriate IED type and rename the IED with the
unique name.
Each IEC 61850 name has to be unique in each level (IED, LD, LN,
DO).
If you wish to import the existing IEC 61850 device CID file to the device, select
Logical Device and import the CID file to it.
6. Import the IED application to logical device LD1 by right-clicking LD1 and
selecting the AR file, which contains the IED application.
7. Set the IP address to SPA-ZC 40x in Object Properties panel.
*
Default Gateway
*
IP Address
*
SNTP Server 1 and 2
*
Subnet mask
Refer to Section 5.5.1. Changing computer's IP address.
8. Set Time Zone Correction.
9. Rename the IED, for example REF545_F1.
10.Adjust IED SPA Communication parameters in the Object Properties panel.
11.Adjust network adapter's IP address to same subnet as SPA-ZC 402. To perform
the operation, open Windows XP Network Connections in Control Panel.
If CID file exists, the IP address is read from the file. Otherwise, the default IP
address of SPA-ZC 402 is 192.168.2.10.
Use IP Query Tool to find out an unknown IP address.
12.Use CID Export tool to transfer the configuration file to SPA-ZC 40x.
13.Export CID or ICD file for the IEC 61850 client.
16
SPA-ZC 402
SPA-ZC 402
SPA/ Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
1MRS755380
Содержание SPA-ZC 402
Страница 2: ......
Страница 6: ...6 ...
Страница 8: ...8 ...
Страница 12: ...12 ...
Страница 14: ...14 ...
Страница 28: ...28 ...
Страница 54: ...54 ...
Страница 58: ...58 ...
Страница 68: ...68 ...
Страница 104: ...104 ...
Страница 106: ...106 ...
Страница 108: ...108 ...
Страница 110: ...110 ...