The following IED-specific settings have to be checked when setting up
REF 541/3/5, REM 543/5 or RET 541/3/5:
*
SPA baud rate and SPA slave number in IED
Baud rate and slave number have to be according to the SPA-ZC 402 configuration
in X3.2/Communication 2.
9.3.
IP Query
By using the IP Query Tool in Communication Engineering Tool (CET) for SPA-ZC
40x, it is possible to see all connected SPA-ZC 40x, devices, their communication
parameters and version information.
Example:
Sending IP query 1
RECEIVED MESSAGE FROM 10.58.125.151:
Mac Address: 00-0C-02-B0-04-89
Subnet Mask: 255.255.255.0
Default Gateway: 10.58.125.150
SNTP servers:10.58.125.150 127.0.0.1
SW_SPATYPE: SPA-ZC40x
SW_NUMBER: 1MRS118533
SW_BUILD: 110
SW_REVISION: B
Compiler DATE_TIME: Nov 28 2005 12:38:02
To use the IP Query Tool:
1. Select
Tools > IP Query Tool
to start the tool, see Fig. 9.3.-1.
Query activates devices from the network until it is stopped.
A060127
Fig. 9.3.-1
Starting the IP Query Tool
2. Select the Network adapter to send a query, see Fig. 9.3.-2.
64
SPA-ZC 402
SPA-ZC 402
SPA/ Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
1MRS755380