Configuring report control blocks
Report control block (RCB) controls spontaneous event reporting. A client can
modify the report sending behavior by setting RCB attributes. The RCB attributes
have suitable default values for the following ABB products: COM600 and
MicroSCADA Pro IEC 61850 client. RCBs are located under the logical device
LD0 and logical node LLN0.
Report
Handler*
Event
Monitor*
Report
Control
event
controls
controls
has association
Reports
Get, Set report
control attribute values
Subscribe for reporting
* local issue
Data
Set
DO
DO
DO
Data
Set
DO
DO
DO
DO
DO
DO
Real
Data
A060032
Fig. 6.10.-1
Reporting model
RCB's have the following properties. To edit the properties, right-click the dataset
and select
Properties
.
*
Buffered reporting
IEC 61850 buffers events also during a communication break. The same
buffering mechanism should be used by all the IED report control blocks.
*
Buffer Time
The default value for buffered reporting is 100 milliseconds (ms). With this
value, RCB waits 100 ms for other events after the first change before sending
the report. Value 0 means that a new change is immediately reported to the client
without waiting for any additional changes. In practice, the buffer time can be
from 0 to a few seconds without a notable effect on the client's event notification
delays. The default values are suitable in most cases.
*
Dataset
The Dataset property defines the data set to be sent as time tagged events with
buffered or unbuffered reporting. Notice that there are few restrictions in the IED
dataset usage to minimize the event load in the IEC 61850 station bus. One
dataset can be used only by one report control block. Additionally, different
datasets used for event reporting should not share the same data objects.
*
Integrity Period
The default value for Integrity Period is 0 ms. If this attribute has a value > 0 ms,
SPA-ZC 402 sends a report with all data listed in a linked data set with this
period. By default, this feature is not enabled, because it generates an
unnecessary load to the server and network. If this feature is used, the properties
of Period Trigger Option in RCB need to be enabled.
*
Report ID
SPA/ Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
SPA-ZC 402
SPA-ZC 402
1MRS755380
Содержание SPA-ZC 402
Страница 2: ......
Страница 6: ...6 ...
Страница 8: ...8 ...
Страница 12: ...12 ...
Страница 14: ...14 ...
Страница 28: ...28 ...
Страница 54: ...54 ...
Страница 58: ...58 ...
Страница 68: ...68 ...
Страница 104: ...104 ...
Страница 106: ...106 ...
Страница 108: ...108 ...
Страница 110: ...110 ...