Table 8.2.-3
Standard tests
Mechanical tests
Vibration tests (sinusoidal)
According to the IEC 60255-21-1, class I
Shock and bump test
According to the IEC 60255-21-2, class I
Table 8.2.-4
Auxiliary power supplies
Type
SPA-ZC 402 xxxA
SPA-ZC 402 xxxC
Input voltage AC
110/120/220/240 V
-
Input voltage DC
110/125/220 V
24/48/64 V
Voltage variation
AC 85...110%, DC 80...120%
of rated value
DC 80...120% of rated value
Burden
<4 W
Ripple in DC auxiliary voltage
Max. 12% of the rated DC value (IEC 60255-11)
Interruption time in auxiliary DC
voltage without resetting
110 V <40 ms
24 V <24 ms