I N S TA L L AT I O N , O P ER AT I O N A N D M A I N T EN A N C E M A N UA L
24
2. 3/8”-16
UNC X 1.0 in
Front View. The exhaust vent can be righ side exit or left side exit (as shown).
Exhaust vent assembly
Note:
All bolts must be tightened; a loose section could let toxic gases escape into the building.
Do not remove exhaust mesh; incandescent particles might escape the MCC in case of an arc fault.
Recommended plenum exhaust “keep clear area”
Clear area
3
SAE grade 5 screws, 30-40 lb-ft torque to bolt MCC Plenum
1. 3/8”-16
UNC X 1.0 in
Opening must be sealed weather tight
(by others).
Building wall.
Vent exhaust.
Optional aditional plenum sections.
Diameter = 96in [2.44m]
2
3/8”-16 UNC X 1.0 in
Length = 180in [4.57m]
—
02
—
03
—
04
—
05