Fig. 13 Fuse replacement
—
Contactor Assembly Ratings
Fig. 12 Contactor
Fuse replacement
Please, refer to the Installation and operation manual for the
controller for fuse replacement procedure.
The fuses replacement and installation are carried out with the
contactor. Fuses are fixed by hexagonal screws. The fuses can be
one barrel or double barrel; both have the same setup to fix, so
additional attachment is not required.
Hardware
Qty. per fuse
Hexagonal 3/8”–16 X 1” UNC head
screw Grade 5
4
Spring washer
4
Flat washer
4
Contactor model
HCV-5HA
HCV-5HAL (Latched Type) HCV-6KAU
HCV-6KALU* (Latched Type)
Rated voltage
2400/4200/6900 V (7.2 kV Max)
2400V/4200/6900 V (7.2 kV Max)
Rated current
400 A
720 A
Interrupting capacity
7000A RMS Symmetrical @5000V Max.
7200 A
4500A RMS Symmetrical @7200V Max.
Peak withstand current
15.8 kA
20 kA
Impulse withstand
60 kV
Permissible switching
1200/Hour
300/Hour
600/Hour
300/Hour
Mechanical life operations
2,500,000
250,000
1,000,000
200,000
Electrical life operations
250,000
250,000
200,000
Closing time
50-110 ms
80-120 ms
Standard opening time
10-60 ms
35-85 ms
Arcing time
10 ms or less
Rated control voltage AC
115/120 or 230/240 V 50/60 Hz
100-240V AC
Rated control voltage DC
120/125 or 240/250 V
100-240V DC
Trip voltage
-
24, 32, 48 ,125, 250 VDC
-
24, 32, 48 ,125, 250 VDC
Control circuit burden (closing)
5.4 A peak @ 120 VAC, 670 VA (AC), 700 W (DC)
6 to 7.0 A @ 120 VAC, 840 VA (AC), 875 W (DC)
Control circuit burden (holding)
0.12 A Avg. @ 120 VAC,85 VA (AC), 85 W (DC)
0.8 to 1 A @ 120 VAC 48 VA
Auxiliary contact arrange
3 N.O. - 3 N.C.
2 N.O.-2 N.C.
3 N.O.-3 N.C.
2 N.O.-2 N.C.
Auxiliary contact rating
10 A, 600 V (NEMA Class A600)