Figure 8-35: Terminal menu option
4.
Type the command
BOOT=COLD
at the terminal prompt (->) (
Figure 8-36: Terminal screen – cold boot
5.
Press
Enter
.
8.5.8
Restart using factory configuration
This procedure uses the 32-bit loader to restore the device's startup configuration to its factory
defaults. Factory defaults can include a generic base configuration or a custom configuration.
Customers can request custom configurations to address specific requirements in addition to the basic
configuration.
Restoring to factory configuration on a device already in service causes service disruption and loss of
network connectivity.
NOTICE – Loss of data.
A restart with factory defaults deletes all data and previous
configurations. Current startup and running configurations are lost. Network communication
parameters are overwritten with factory defaults as well. Perform the procedures in section
Preserve data and configuration before restoring factory defaults. We do not recommend
triggering the restart remotely on a network connection because the device might lose
connectivity. You must have physical access to the device to reconfigure.
To restore factory configuration:
1.
Launch PCCU.
2.
Click the
32-Bit Loader
icon in the toolbar. A message box displays.
3.
Click
Yes
.
4.
Verify the connection setup information and click
Connect
. The Loader screen displays.
5.
Click
Services
>
Restart
in the menu bar and select
Restart
using Factory configuration
from the drop-down list (