2105552MNAE | RMC-100 |
133
Figure 7-9: Low value current reading verification
16.
Keep the default target low value of 0 (
) or type an appropriate value for your
scenario. This example uses 0 for a 0-1500 PSI measurement range. A voltage value of 1 Vdc
represents 0 PSI.
Figure 7-10: Default low calibration value for measurement range
17.
Click
OK
. The Reading column updates to reflect the signal value associated with the low value
of the range (