Figure 8-15: Locate the saved configuration (default directory)
8.2
Restore the device configuration
Use the device loader to restore the configuration on the controller with a previously saved
configuration package. Verify that the configuration package originated from the same unit. Then
restore the device in the event of file corruption or other problems.
NOTICE –Loss of data.
When you restore the configuration, the loader sends the
configuration package to replace the controller's existing startup configuration. The
controller automatically uses the new startup configuration to restart (cold restart) and
removes the previous startup configuration.
Before restoring the configuration on the controller, perform the procedure in section
Collect data to collect the measurement data and avoid data loss. It might be necessary to
preserve the existing configuration if technical support needs to troubleshoot configuration
issues. If necessary, perform the procedures in section
configuration and section
Save the startup (cold) configuration to the PC or laptop.
To restore the device configuration file:
1.
Verify that PCCU32 is not connected to the controller. If it is still connected, click the
Disconnect icon on the toolbar.
2.
Click the 32 Bit Loader icon in the toolbar. A warning dialog to collect data displays.
3.
Click
Yes
. The Connection Setup dialog displays.
4.
Verify, select or type the connection setup parameters into the entry fields and click
Connect
.
The main loader screen displays when the controller connects.
5.
Click
Browse
.
6.
Locate and select the configuration file package, then click
Open
. The package details display
in the Package field (