2105552MNAE | RMC-100 |
161
Figure 7-50: Calibrated AO example
16.
Type different values into the %FS or mA fields to verify the calibration. The controller
produces the specified current output at the AO. For example:
a.
Select the
mA
field. The Enter Value for AO (mA) box displays (