2105552MNAE | RMC-100 |
173
The running (warm) might contain calibration files. These files also save to the startup
configuration during the update. Calibration files link with the device’s electronic board serial
number and do not apply to any other device.
To update the startup configuration:
1.
Launch PCCU32 and click the Entry icon on the toolbar.
2.
Click the top item on the navigation tree. The Station Setup tab displays.
3.
Scroll down to the Backup section (
Figure 8-5: Update cold start configuration
4.
Click the
Update Cold Start Configuration Value
cell and select
Delete and Re-create
TfCold
from the drop-down list.
5.
Click
Send
.
6.
Click
Close
to exit the Station Setup screen and Entry Setup mode.
7.
Click
Close
to disconnect PCCU32 from the controller.
8.
Proceed to
section 8.1.2.2, Save the startup (cold) configuration to the PC or laptop
.
8.1.2.2
Save the startup (cold) configuration to the PC or laptop
This procedure saves the startup (cold) configuration from the device to a laptop or PC using the 32-
Bit Loader. This requires a separate connection established from the loader, not from entry mode.
IMPORTANT NOTE:
If calibration files are in the startup configuration, they are automatically in
the configuration package.
The saved calibration files link to the device’s electronic board serial number and do not apply to
any other device.
To save the device configuration:
1.
Verify that PCCU32 is not connected to the controller. If it is still connected, click the
Disconnect icon on the toolbar.
2.
Click the
32-Bit Loader
icon in the toolbar (
Figure 8-6: 32 Bit Loader icon
Figure 8-7: Warning to collect data and update configuration
3.
Click
Yes
. The Connection Setup dialog displays (