2105552MNAE | RMC-100 |
147
26.
Click
50% Cal Point
. The Enter 50% Calibration Value dialog displays with the target mid
value automatically calculated. For example, 750.000 for the range value of 1500 (
27.
Adjust the calibrator to apply the mid-range value (50%) of the signal range. For example, if
the signal range of the external device is 4 to 20 mA, apply 12 mA.
28.
Observe the value in the Current Reading field (
). The displayed voltage value for
12 mA is approximately 3 Vdc When the value stabilizes, click
OK
.
Figure 7-31: Mid (50%) calibration value
29.
Click
OK
when the Calibration Complete message displays (