Table 74. Event recorder
Function
Value
Buffer capacity
Maximum number of events in disturbance report
150
Maximum number of disturbance reports
100
Resolution
1 ms
Accuracy
Depending on time
synchronizing
Table 75. Trip value recorder
Function
Value
Buffer capacity
Maximum number of analog inputs
30
Maximum number of disturbance reports
100
Table 76. Disturbance recorder
Function
Value
Buffer capacity
Maximum number of analog inputs
40
Maximum number of binary inputs
96
Maximum number of disturbance reports
100
Maximum total recording time (3.4 s recording time and maximum number
of channels, typical value)
340 seconds (100 recordings) at 50 Hz
280 seconds (80 recordings) at 60 Hz
Bay control REC670
1MRK511232-BEN E
Pre-configured
Product version: 1.2