Table 13. IOM - Binary input/output module
Quantity
Rated value
Nominal range
Binary inputs
8
-
DC voltage, RL
24/30 V
48/60 V
110/125 V
220/250 V
RL
±
20%
RL
±
20%
RL
±
20%
RL
±
20%
Power consumption
24/30 V, 50 mA
48/60 V, 50 mA
110/125 V, 50 mA
220/250 V, 50 mA
220/250 V, 110 mA
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
max. 0.5 W/input
-
Counter input frequency
10 pulses/s max
Oscillating signal discriminator
Blocking settable 1-40 Hz
Release settable 1-30 Hz
Debounce filter
Settable 1-20 ms
Maximum 176 binary input channels may
be activated simultaneously with influencing
factors within nominal range.
Table 14. IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity
Trip and signal relays
Fast signal relays (parallel
reed relay)
Binary outputs
10
2
Max system voltage
250 V AC, DC
250 V DC
Test voltage across open contact, 1 min
1000 V rms
800 V DC
Current carrying capacity
Per relay, continuous
Per relay, 1 s
Per process connector pin, continuous
8 A
10 A
12 A
8 A
10 A
12 A
Making capacity at inductive load with L/R>10 ms
0.2 s
1.0 s
30 A
10 A
0.4 A
0.4 A
Making capacity at resistive load
0.2 s
1.0 s
30 A
10 A
220–250 V/0.4 A
110–125 V/0.4 A
48–60 V/0.2 A
24–30 V/0.1 A
Breaking capacity for AC, cos φ > 0.4
250 V/8.0 A
250 V/8.0 A
Breaking capacity for DC with L/R < 40 ms
48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
Maximum capacitive load
-
10 nF
Bay control REC670
1MRK511232-BEN E
Pre-configured
Product version: 1.2
32