20. Technical data
General
Definitions
Reference value
The specified value of an influencing factor to which are referred the characteristics of the equipment
Nominal range
The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the
specified requirements
Operative range
The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform its
intended functions according to the specified requirements
Energizing quantities, rated values and limits
Analog inputs
Table 6. TRM - Energizing quantities, rated values and limits for protection transformer modules
Quantity
Rated value
Nominal range
Current
I
r
= 1 or 5 A
(0.2-40) × I
r
Operative range
(0-100) x I
r
Permissive overload
4 × I
r
cont.
100 × I
r
for 1 s
*)
Burden
< 150 mVA at I
r
= 5 A
< 20 mVA at I
r
= 1 A
Ac voltage
U
r
= 110 V
0.5–288 V
Operative range
(0–340) V
Permissive overload
420 V cont.
450 V 10 s
Burden
< 20 mVA at 110 V
Frequency
f
r
= 50/60 Hz
± 5%
*)
max. 350 A for 1 s when COMBITEST test switch is included.
Bay control REC670
1MRK511232-BEN E
Pre-configured
Product version: 1.2
ABB
29
Содержание Relion 670 series REC670
Страница 1: ...Relion 670 series Bay control REC670 Pre configured Product Guide ...
Страница 83: ...83 ...