Table 40. Broken conductor check BRCPTOC
Function
Range or value
Accuracy
Minimum phase current for operation
(5–100)% of
IBase
± 0.1% of I
r
Unbalance current operation
(0–100)% of maximum current
± 0.1% of I
r
Timer
(0.00-6000.00) s
± 0.5% ± 10 ms