Table 43. Two step residual overvoltage protection ROV2PTOV
Function
Range or value
Accuracy
Operate voltage, step 1 and step 2
(1-200)% of
UBase
± 0.5% of U
r
at U < U
r
± 1.0% of U at U > U
r
Absolute hysteresis
(0–100)% of
UBase
± 0.5% of U
r
at U < U
r
± 1.0% of U at U > U
r
Inverse time characteristics for low and high step, see table
-
Definite time setting, step 1
(0.00–6000.00) s
± 0.5% ± 10 ms
Definite time setting
(0.000–60.000) s
± 0.5% ± 10 ms
Minimum operate time
(0.000-60.000) s
± 0.5% ± 10 ms
Operate time, start function
25 ms typically at 0 to 2 x U
set
-
Reset time, start function
25 ms typically at 2 to 0 x U
set
-
Critical impulse time
10 ms typically at 0 to 2 x U
set
-
Impulse margin time
15 ms typically
-
Table 44. Voltage differential protection VDCPTOV
Function
Range or value
Accuracy
Voltage difference for alarm and
trip
(0.0–100.0) % of
UBase
± 0.5 % of U
r
Under voltage level
(0.0–100.0) % of
UBase
± 0.5% of U
r
Timers
(0.000–60.000)s
± 0.5% ± 10 ms
Table 45. Loss of voltage check LOVPTUV
Function
Range or value
Accuracy
Operate voltage
(0–100)% of UBase
± 0.5% of U
r
Pulse timer
(0.050–60.000) s
± 0.5% ± 10 ms
Timers
(0.000–60.000) s
± 0.5% ± 10 ms
Bay control REC670
1MRK511232-BEN E
Pre-configured
Product version: 1.2
ABB
47