Table 70. Disturbance report DRPRDRE
Function
Range or value
Accuracy
Pre-fault time
(0.05–9.90) s
-
Post-fault time
(0.1–10.0) s
-
Limit time
(0.5–10.0) s
-
Maximum number of recordings
100, first in - first out
-
Time tagging resolution
1 ms
Maximum number of analog inputs
30 + 10 (ex internally
derived)
-
Maximum number of binary inputs
96
-
Maximum number of phasors in the Trip Value recorder per recording
30
-
Maximum number of indications in a disturbance report
96
-
Maximum number of events in the Event recording per recording
150
-
Maximum number of events in the Event list
1000, first in - first out
-
Maximum total recording time (3.4 s recording time and maximum number of
channels, typical value)
340 seconds (100 recordings) at
50 Hz, 280 seconds (80
recordings) at 60 Hz
-
Sampling rate
1 kHz at 50 Hz
1.2 kHz at 60 Hz
-
Recording bandwidth
(5-300) Hz
-
Table 71. Fault locator LMBRFLO
Function
Value or range
Accuracy
Reactive and resistive reach
(0.001-1500.000) Ω/phase
± 2.0% static accuracy
± 2.0% degrees static angular accuracy
Conditions:
Voltage range: (0.1-1.1) x U
r
Current range: (0.5-30) x I
r
Phase selection
According to input signals
-
Maximum number of fault
locations
100
-
Table 72. Event list
Function
Value
Buffer capacity
Maximum number of events in the list
1000
Resolution
1 ms
Accuracy
Depending on time synchronizing
Table 73. Indications
Function
Value
Buffer capacity
Maximum number of indications presented for single disturbance
96
Maximum number of recorded disturbances
100
Bay control REC670
1MRK511232-BEN E
Pre-configured
Product version: 1.2
ABB
61