Section 13
Metering
13.1
Pulse counter PCGGIO
13.1.1
Identification
GUID-50478353-2EE5-45ED-8A89-4EB0A0F71314 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Pulse counter
PCGGIO
S00947 V1 EN-US
-
13.1.2
Application
M13395-3 v5
Pulse counter (PCGGIO) function counts externally generated binary pulses, for instance pulses
coming from an external energy meter, for calculation of energy consumption values. The pulses
are captured by the binary input module (BIO), and read by the PCGGIO function. The number of
pulses in the counter is then reported via the station bus to the substation automation system or
read via the station monitoring system as a service value. When using IEC 61850–8–1, a scaled
service value is available over the station bus.
The normal use for this function is the counting of energy pulses from external energy meters. An
optional number of inputs from the binary input module in IED can be used for this purpose with a
frequency of up to 10 Hz. PCGGIO can also be used as a general purpose counter.
13.1.3
Setting guidelines
M13396-4 v5
From PCM600, these parameters can be set individually for each pulse counter:
•
Operation: Disabled/Enabled
•
tReporting: 0-3600s
•
EventMask: NoEvents/ReportEvents
The configuration of the inputs and outputs of PCGGIO function block is made with PCM600.
On the binary input output module (BIO), the debounce filter default time is set to 5 ms, that is,
the counter suppresses pulses with a pulse length less than 5 ms. The binary input channels on the
binary input output module (BIO) have individual settings for debounce time, oscillation count and
oscillation time. The values can be changed in the local HMI and PCM600 under Main menu/
Configuration/I/O modules
The debunce time should be set to the same value for all channels on the board
1MRK 505 287-UUS B
Section 13
Metering
Busbar protection REB650
211
Application manual
© Copyright 2013 ABB. All rights reserved
Содержание RELION 650 SERIES
Страница 1: ...Relion 650 SERIES Busbar protection REB650 Version 1 3 ANSI Application manual...
Страница 2: ......
Страница 22: ...16...
Страница 34: ...28...
Страница 56: ...50...
Страница 64: ...58...
Страница 76: ...70...
Страница 120: ...114...
Страница 184: ...178...
Страница 216: ...210...
Страница 220: ...214...
Страница 254: ...248...
Страница 261: ...255...