Trip value rec
Sequential of
events
Event recorder
Indications
Disturbance
recorder
A1-4RADR
B1-6RBDR
Disturbance Report
Binary signals
Analog signals
A4RADR
B6RBDR
DRPRDRE
ANSI09000337-1-en.vsd
ANSI09000337 V1 EN-US
Figure 101: Disturbance report functions and related function blocks
For Disturbance report function there are a number of settings which also influences the sub-
functions.
Three LED indications placed above the LCD screen makes it possible to get quick status
information about the IED.
Green LED:
Steady light
In Service
Flashing light
Internal failure
Dark
No power supply
Yellow LED:
Function controlled by SetLEDn
setting in Disturbance report
function.
Red LED:
Function controlled by SetLEDn
setting in Disturbance report
function.
Operation
M12179-82 v5
The operation of Disturbance report function DRPRDRE has to be set
Enabled or Disabled. If
Disabled is selected, note that no disturbance report is registered, and none sub-function will
operate (the only general parameter that influences Sequential of events).
Operation = Disabled:
1MRK 505 287-UUS B
Section 12
Monitoring
Busbar protection REB650
201
Application manual
© Copyright 2013 ABB. All rights reserved
Содержание RELION 650 SERIES
Страница 1: ...Relion 650 SERIES Busbar protection REB650 Version 1 3 ANSI Application manual...
Страница 2: ......
Страница 22: ...16...
Страница 34: ...28...
Страница 56: ...50...
Страница 64: ...58...
Страница 76: ...70...
Страница 120: ...114...
Страница 184: ...178...
Страница 216: ...210...
Страница 220: ...214...
Страница 254: ...248...
Страница 261: ...255...