10.1.3.3
Single circuit breaker with double busbar, internal voltage selection
GUID-1DE55058-62A0-4C9A-9C6A-ACA61B7780D4 v4
Bus 1
Bus 2
Line
Fuse
VT
Fuse
VT
ANSI10000196-2-en.vsd
SMAI
GRP_OFF
SMAI
SMAI
VBus1
VBus2
VLine
Fuse
VT
SESRSYN (25)
V3PB1*
V3PB2*
V3PL1*
V3PL2*
BLOCK
BLKSYNCH
BLKSC
BLKENERG
BUS1_OP
BUS1_CL
BUS2_OP
BUS2_CL
LINE1_OP
LINE1_CL
LINE2_OP
LINE2_CL
VB1OK
VB1FF
VB2OK
VB2FF
VL1OK
VL1FF
VL2OK
VL2FF
STARTSYN
TSTSYNCH
TSTSC
TSTENERG
AENMODE
MENMODE
SYNOK
AUTOSYOK
AUTOENOK
MANSYOK
MANENOK
TSTSYNOK
TSTAUTSY
TSTMANSY
TSTENOK
VSELFAIL
B1SEL
B2SEL
L1SEL
L2SEL
SYNPROGR
SYNFAIL
FRDIFSYN
FRDERIVA
VOKSC
VDIFFSC
FRDIFFA
PHDIFFA
FRDIFFM
PHDIFFM
INADVCLS
VDIFFME
FRDIFFME
PHDIFFME
Vbus
VLine
MODEAEN
MODEMEN
189
289
BKR1
52
ANSI10000196 V2 EN-US
Figure 47: Connection of the SESRSYN (25) function block in a single breaker, double busbar
arrangement with internal voltage selection.
When internal voltage selection is needed, the voltage transformer circuit connections are made
according to figure
. The voltage from busbar1 VT is connected to V3PB1 and the voltage from
busbar2 VT is connected to V3PB2. The voltage from the line VT is connected to V3PL1. The
positions of the disconnectors and VT fuses shall be connected as shown in figure
selection parameter
CBConfig is set to Double bus.
M12329-3 v6
M12330-3 v6
10.1.4
Setting guidelines
M12550-3 v9
The setting parameters for the Synchronizing, synchronism check and energizing check function
SESRSYN (25) are set via the local HMI (LHMI) or PCM600.
This setting guidelines describes the settings of the SESRSYN (25) function via the LHMI.
Common base IED value for primary voltage (
VBase) is set in a Global base value function,
GBASVAL, found under Main menu/Configuration/Power system/Global base values/
X:GBASVAL/VBase. GBASVAL has six instances which can be set independently of each other. The
SESRSYN (25) function has one setting for the bus reference voltage (
GblBaseSelBus) and one
setting for the line reference voltage (
GblBaseSelLine) which independently of each other can be
set to select one of the six GBASVAL functions used for reference of base values. This means that
the reference voltage of bus and line can be set to different values. The settings for the SESRSYN
(25) function found under Main menu/Settings/Control/SESRCYN(25,SYNC)/X:SESRSYN has
been divided into four different setting groups: General, Synchronizing, Synchrocheck and
Energizing check.
1MRK 505 287-UUS B
Section 10
Control
Busbar protection REB650
123
Application manual
© Copyright 2013 ABB. All rights reserved
Содержание RELION 650 SERIES
Страница 1: ...Relion 650 SERIES Busbar protection REB650 Version 1 3 ANSI Application manual...
Страница 2: ......
Страница 22: ...16...
Страница 34: ...28...
Страница 56: ...50...
Страница 64: ...58...
Страница 76: ...70...
Страница 120: ...114...
Страница 184: ...178...
Страница 216: ...210...
Страница 220: ...214...
Страница 254: ...248...
Страница 261: ...255...