10.1.3.1
Single circuit breaker with single busbar
M12324-3 v9
Line
Bus 1
Fuse
VT
ANSI11000164_2_en.vsd
VBus
VLine
Fuse
VT
SMAI
SMAI
GRP_OFF
SESRSYN (25)
V3PB1*
V3PB2*
V3PL1*
V3PL2*
BLOCK
BLKSYNCH
BLKSC
BLKENERG
BUS1_OP
BUS1_CL
BUS2_OP
BUS2_CL
LINE1_OP
LINE1_CL
LINE2_OP
LINE2_CL
VB1OK
VB1FF
VB2OK
VB2FF
VL1OK
VL1FF
VL2OK
VL2FF
STARTSYN
TSTSYNCH
TSTSC
TSTENERG
AENMODE
MENMODE
SYNOK
AUTOSYOK
AUTOENOK
MANSYOK
MANENOK
TSTSYNOK
TSTAUTSY
TSTMANSY
TSTENOK
VSELFAIL
B1SEL
B2SEL
L1SEL
L2SEL
SYNPROGR
SYNFAIL
FRDIFSYN
FRDERIVA
VOKSC
VDIFFSC
FRDIFFA
PHDIFFA
FRDIFFM
PHDIFFM
INADVCLS
VDIFFME
FRDIFFME
PHDIFFME
Vbus
VLine
MODEAEN
MODEMEN
189
BKR1
52
ANSI11000164 V2 EN-US
Figure 45: Connection of SESRSYN (25) function block in a single busbar arrangement
Figure
illustrates connection principles. For the SESRSYN (25) function there is one voltage
transformer on each side of the circuit breaker. The voltage transformer circuit connections are
straightforward; no special voltage selection is necessary.
The voltage from busbar VT is connected to V3PB1 and the voltage from the line VT is connected
to V3PL1. The positions of the VT fuses shall also be connected as shown above. The voltage
selection parameter
CBConfig is set to No voltage sel.
1MRK 505 287-UUS B
Section 10
Control
Busbar protection REB650
121
Application manual
© Copyright 2013 ABB. All rights reserved
Содержание RELION 650 SERIES
Страница 1: ...Relion 650 SERIES Busbar protection REB650 Version 1 3 ANSI Application manual...
Страница 2: ......
Страница 22: ...16...
Страница 34: ...28...
Страница 56: ...50...
Страница 64: ...58...
Страница 76: ...70...
Страница 120: ...114...
Страница 184: ...178...
Страница 216: ...210...
Страница 220: ...214...
Страница 254: ...248...
Страница 261: ...255...