SXCBR
SCSWI
SCILO
(3)
SCSWI
SCILO
(3)
SXSWI
-BKR1
-189
-989
IEC 61850
QCBAY
ANSI10000198_2_en.vsd
52
ANSI10000198 V2 EN-US
Figure 49: Signal flow between apparatus control function blocks
The IEC 61850 communication has always priority over binary inputs, e.g. a block
command on binary inputs will not prevent commands over IEC 61850.
Accepted originator categories for PSTO
If the requested command is accepted due to the authority allocation control, the respective value
will change. Otherwise the attribute
blocked-by-switcing-hierarky is set in the cause signal. If the
PSTO value is changed under a command, then the command is reset.
The accepted originator categories for each PSTO value are shown in
Table 15: Accepted originator categories for each PSTO
PermittdSourceToOperate
Originator
0 = Off
4,5,6
1 = Local
1,4,5,6
2 = Remote
2,3,4,5,6
Table continues on next page