6.1.3.1
Creating disturbance recordings
Normally disturbance recordings are triggered by the IED applications but the
recording can also be triggered manually.
Set the DRRDRE
Operation
to “On” via the LHMI or PCM600. At
least one channel has to be connected.
1.
Select
Main menu/Disturbance records
.
2.
Select
Manual Trig
with
or
.
3.
Press
to execute manual triggering.
A071208 V3 EN
Figure 50:
Manual triggering
The disturbance recorder is now triggered.
6.1.3.2
Monitoring disturbance recorder data
Read individual disturbance recordings from the IED with the PCM600 software to
monitor disturbance recorder data.
1.
Select
Main menu/Disturbance records
.
All disturbance records are listed.
2.
Scroll the view with
or
.
Section 6
1MRS756509 E
Operating procedures
70
630 series