![ABB Relion 615 series Скачать руководство пользователя страница 97](http://html1.mh-extra.com/html/abb/relion-615-series/relion-615-series_modbus-point-list-manual_3381023097.webp)
2.4.1.38
LD0.RESCMMXU1 Residual current demand value (1) – IG-1
Table 161:
LD0.RESCMMXU1 Residual current demand value (1) – IG-1
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.RCAVMMXU1
Demand value
1989
u16
1000
.A.res.cVal.mag
I_DMD_RES
Residual amplitude
0.00…50.0
[xIn]
1990
Year - month
1991
Day - hour
1992
Minute - second
1993
Milliseconds
1994
Time quality
LD0.RCMAMMXU1
Max. demand value
1995
u16
1000
.A.res.cVal.mag
Max demand Io
Residual amplitude
0.00…50.0
[xIn]
1996
Year - month
1997
Day - hour
1998
Minute - second
1999
Milliseconds
2000
Time quality
LD0.RCMIMMXU1
Min. demand value
u16
1000
.A.res.cVal.mag
Min demand Io
Residual amplitude
0.00…50.0
[xIn]
2.4.1.39
LD0.RESCMMXU1 Residual current measurement (1) – IG-1
Table 162:
LD0.RESCMMXU1 Residual current measurement (1) – IG-1
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.RESCMMXU1
Residual current (1)
141
u16
1000
.A.res.instCVal.mag
I0_INST
- amplitude
0.00...40.0
[xIn]
1MAC252756-MB B
Section 2
Modbus data mappings
REM615 ANSI
91
Point List Manual
Содержание Relion 615 series
Страница 1: ...RELION 615 SERIES Motor Protection and Control REM615 ANSI Modbus Point List Manual...
Страница 2: ......
Страница 14: ...8...
Страница 114: ...108...