![ABB Relion 615 series Скачать руководство пользователя страница 86](http://html1.mh-extra.com/html/abb/relion-615-series/relion-615-series_modbus-point-list-manual_3381023086.webp)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
9487
i16
100
.DifACAngVAB1.mag
Angle UAB-IC(1)
-180.00…
180.00 [deg]
9488
i16
100
.DifANAngVN2.mag.
Angle Uo-Io(2)
-180.00…
180.00 [deg]
9489
i16
100
.DifAAAngVBC2.mag.
Angle UBC-IA(2)
-180.00…
180.00 [deg]
9490
i16
100
.DifABAngVCA2.mag
Angle UCA-IB(2)
-180.00…
180.00 [deg]
9491
i16
100
.DifACAngVAB2.mag
Angle UAB-IC(2)
-180.00…
180.00 [deg]
2.4.1.14
Protection relay's real-time clock (in local time mode) - read and write
(synchronize)
Table 137:
Protection relay's real-time clock (in local time mode) - read and write (synchronize)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
9201
Control register
0...2
1)
9202
Year
2000...2999
9203
Month
1...12
9204
Day
1...31
9205
Hour
0...23
9206
Minute
0...59
9207
Second
0...59
9208
Millisecond
0…999
1) See the technical manual.
2.4.1.15
Protection relay's real-time clock (in UTC time mode) - read and write
(synchronize)
Table 138:
Protection relay's real-time clock (in UTC time mode) - read and write (synchronize)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
9211
Control register
0...2
1)
9212
Year
2000...2999
9213
Month
1...12
9214
Day
1...31
9215
Hour
0...23
Table continues on next page
Section 2
1MAC252756-MB B
Modbus data mappings
80
REM615 ANSI
Point List Manual
Содержание Relion 615 series
Страница 1: ...RELION 615 SERIES Motor Protection and Control REM615 ANSI Modbus Point List Manual...
Страница 2: ......