![ABB Relion 615 series Скачать руководство пользователя страница 31](http://html1.mh-extra.com/html/abb/relion-615-series/relion-615-series_modbus-point-list-manual_3381023031.webp)
2.3.1.13
CTRL.ESXSWI1 Grounding switch control (1) – 29GS-1
Table 16:
CTRL.ESXSWI1 Grounding switch control (1) – 29GS-1
BitA
RegA
IEC 61850 name
SA name
Description
Values
CTRL.ESXSWI1
POSITION
3496
218.08
.Pos.stVal.Close
-
Close bit
1=Close
3497
218.09
.Pos.stVal.Open
-
Open bit
1=Open
3498
218.10
.Pos.stVal.Fault
-
Fault bit
1=Pos(00/11)
3499
218.11
.Pos.stSeld
-
Control selected
1=Selected
CTRL.ESCILO1
3500
218.12
.EnaOpn.stVal
ENA_OPEN
Open enabled
1=Enabled
3501
218.13
.EnaCls.stVal
ENA_CLOSE
Close enabled
1=Enabled
CTRL.ESXSWI1
3502
218.14
.BlkOpn.stVal
BLK_OPEN
Open blocked
1=Blocked
3503
218.15
.mcd
3504
219.00
.BlkCls.stVal
BLK_CLOSE
Close blocked
1=Blocked
3505
219.01
.mcd
CTRL.ESCILO1
3506
219.02
.ItlByps.stVal
ITL_BYPASS
Interlock bypass
1=Bypass
3507
219.03
.mcd
2.3.1.14
LD0.ARCSARC1 Arc protection (1) – AFD-1
Table 17:
LD0.ARCSARC1 Arc protection (1) – AFD-1
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.ARCSARC11
2978
186.02
.FADet.stVal
ARC_FLT_DET
Arc detected
1=Detected
2979
186.03
.mcd
LD0.ARCPTRC11
2982
186.06
.Op.general
TRIP
Stage trip
1=Trip
2983
186.07
.mcd
1MAC252756-MB B
Section 2
Modbus data mappings
REM615 ANSI
25
Point List Manual
Содержание Relion 615 series
Страница 1: ...RELION 615 SERIES Motor Protection and Control REM615 ANSI Modbus Point List Manual...
Страница 2: ......
Страница 14: ...8...
Страница 114: ...108...