2.3.1.10
CTRL.DCXSWI2 Disconnector control (2) – 29DS-2
Table 13:
CTRL.DCXSWI2 Disconnector control (2) – 29DS-2
BitA
RegA
IEC 61850 name
SA name
Description
Values
CTRL.DCXSWI2
POSITION
3484
217.12
.Pos.stVal.Close
-
Close bit
1=Close
3485
217.13
.Pos.stVal.Open
-
Open bit
1=Open
3486
217.14
.Pos.stVal.Fault
-
Fault bit
1=Pos(00/11)
3487
217.15
.Pos.stSeld
-
Control selected
1=Selected
CTRL.DCCILO2
3488
218.00
.EnaOpn.stVal
ENA_OPEN
Open enabled
1=Enabled
3489
218.01
.EnaCls.stVal
ENA_CLOSE
Close enabled
1=Enabled
CTRL.DCXSWI2
3490
218.02
.BlkOpn.stVal
BLK_OPEN
Open blocked
1=Blocked
3491
218.03
.mcd
3492
218.04
.BlkCls.stVal
BLK_CLOSE
Close blocked
1=Blocked
3493
218.05
.mcd
CTRL.DCCILO2
3494
218.06
.ItlByps.stVal
ITL_BYPASS
Interlock bypass
1=Bypass
3495
218.07
.mcd
2.3.1.11
CTRL.ESSXSWI1 Grounding switch indication (1) – 29GS-1
Table 14:
CTRL.ESSXSWI1 Grounding switch indication (1) – 29GS-1
BitA
RegA
IEC 61850 name
SA name
Description
Values
CTRL.ESSXSWI1
POSITION
2801
175.01
.Pos.stVal.Close
-
Close bit
1=Close
2802
175.02
.Pos.stVal.Open
-
Open bit
1=Open
2803
175.03
.Pos.stVal.Fault
-
Fault bit
1=Pos(00/11)
2.3.1.12
CTRL.ESSXSWI2 Grounding switch indication (2) – 29GS-2
Table 15:
CTRL.ESSXSWI2 Grounding switch indication (2) – 29GS-2
BitA
RegA
IEC 61850 name
SA name
Description
Values
CTRL.ESSXSWI2
POSITION
2807
175.07
.Pos.stVal.Close
-
Close bit
1=Close
2808
175.08
.Pos.stVal.Open
-
Open bit
1=Open
2809
175.09
.Pos.stVal.Fault
-
Fault bit
1=Pos(00/11)
Section 2
1MAC252756-MB B
Modbus data mappings
24
REM615 ANSI
Point List Manual