![ABB Relion 615 series Скачать руководство пользователя страница 108](http://html1.mh-extra.com/html/abb/relion-615-series/relion-615-series_modbus-point-list-manual_3381023108.webp)
0xA
CS
IEC 61850 name
SA name
Description
Values
2072
2.12
.RsSprChaTm.Oper.ctlVa
l
Reset CB spring charge time
1=Reset
LD0.RESCMMXU1
2073
2.13
.RecRs.Oper.ctlVal
Reset Io (1) max demands
1=Reset
LD0.RESVMMXU1
2074
2.14
.RecRs.Oper.ctlVal
Reset Uo (1) max demands
1=Reset
2.5.2
CTRL.CBCSWI1 Circuit breaker control (1)
Table 182:
CTRL.CBCSWI1 Circuit breaker control (1)
0xA
CS
IEC 61850 name
SA name
Description
Values
CTRL.CBCSWI1
2048
1.00
.Pos.Oper.ctlVal
Select open
1=Select
2049
1.01
.Pos.Oper.ctlVal
Select close
1=Select
2050
1.02
.Pos.Oper.ctlVal
Cancel selection
1=Cancel
2051
1.03
.Pos.Oper.ctlVal
Execute selection
1=Execute
2052
1.04
.Pos.Oper.ctlVal
Direct open
1=Open
2053
1.05
.Pos.Oper.ctlVal
Direct close
1=Close
2.5.3
CTRL.DCXSWI1 Disconnector control (1) – 29DS-1
Table 183:
CTRL.DCXSWI1 Disconnector control (1) – 29DS-1
0xA
CS
IEC 61850 name
SA name
Description
Values
CTRL.DCCSWI1
2144
7.00
.Pos.Oper.ctlVal
Select open
1=Select
2145
7.01
.Pos.Oper.ctlVal
Select close
1=Select
2146
7.02
.Pos.Oper.ctlVal
Cancel selection
1=Cancel
2147
7.03
.Pos.Oper.ctlVal
Execute selection
1=Execute
2148
7.04
.Pos.Oper.ctlVal
Direct open
1=Open
2149
7.05
.Pos.Oper.ctlVal
Direct close
1=Close
Section 2
1MAC252756-MB B
Modbus data mappings
102
REM615 ANSI
Point List Manual
Содержание Relion 615 series
Страница 1: ...RELION 615 SERIES Motor Protection and Control REM615 ANSI Modbus Point List Manual...
Страница 2: ......
Страница 14: ...8...
Страница 114: ...108...