![ABB Relion 615 series Скачать руководство пользователя страница 101](http://html1.mh-extra.com/html/abb/relion-615-series/relion-615-series_modbus-point-list-manual_3381023101.webp)
RegA
Type
Scale
IEC 61580 name
SA name
Description
Values
2036
i16
1
.AnIn6.mag
AI_VAL6
RTD input 6 in ohms
-/+ 10000.00
2037
i16
1
.AnIn7.mag
AI_VAL7
RTD input 7 in ohms
-/+ 10000.00
2038
i16
1
.AnIn8.mag
AI_VAL8
RTD input 8 in ohms
-/+ 10000.00
2.4.2
Unmapped registers
Unmapped registers are register data that have no initial Modbus mapping locations, but
can be added to the user-definable Modbus area using the Communication Management
tool in PCM600. The initial register type settings of these objects have little meaning,
since it is always possible to redefine the settings completely for the user-definable
register.
2.4.2.1
CTRL.LLN0 Local, Remote, Station, Off and Combinations
Table 170:
CTRL.LLN0 Local, Remote, Station, Off and Combinations
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
CTRL.LLN0
u16
1
.LocKeyHMI.stVal
0=Off; 1=Loc; 2=Rem; 3=Stat;
4=L+R; 5=L+S; 6=L+S+R; 7=S
+R
0…7
2.4.2.2
LD0.LLN0/LPHD1/LDEV1 System values
Table 171:
LD0.LLN0/LPHD1/LDEV1 System values
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.LLN0
u16
1
.ParChgCnt.stVal
Num. of setting changes
0…65535
2.4.2.3
LD0.MVI4GAPC1 Integer value move (1) – MVI4-1
Table 172:
LD0.MVI4GAPC1 Integer value move (1) – MVI4-1
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.MVI4GAPC1
i32
1
.ISCS01.stVal
OUT1
- Integer value 1 (high)
-/
+2147483647
- Low word
i32
1
.ISCS02.stVal
OUT2
- Integer value 2 (high)
-/
+2147483647
Table continues on next page
1MAC252756-MB B
Section 2
Modbus data mappings
REM615 ANSI
95
Point List Manual