2.5.4
CTRL.DCXSWI2 Disconnector control (2) – 29DS-2
Table 184:
CTRL.DCXSWI2 Disconnector control (2) – 29DS-2
0xA
CS
IEC 61850 name
SA name
Description
Values
CTRL.DCCSWI2
2150
7.06
.Pos.Oper.ctlVal
Select open
1=Select
2151
7.07
.Pos.Oper.ctlVal
Select close
1=Select
2152
7.08
.Pos.Oper.ctlVal
Cancel selection
1=Cancel
2153
7.09
.Pos.Oper.ctlVal
Execute selection
1=Execute
2154
7.10
.Pos.Oper.ctlVal
Direct open
1=Open
2155
7.11
.Pos.Oper.ctlVal
Direct close
1=Close
2.5.5
CTRL.ESXSWI1 Grounding switch control (1) – 29GS-1
Table 185:
CTRL.ESXSWI1 Grounding switch control (1) – 29GS-1
0xA
CS
IEC 61850 name
SA name
Description
Values
CTRL.ESXSWI1
2054
1.06
.Pos.Oper.ctlVal
Select open
1=Select
2055
1.07
.Pos.Oper.ctlVal
Select close
1=Select
2056
1.08
.Pos.Oper.ctlVal
Cancel selection
1=Cancel
2057
1.09
.Pos.Oper.ctlVal
Execute selection
1=Execute
2058
1.10
.Pos.Oper.ctlVal
Direct open
1=Open
2059
1.11
.Pos.Oper.ctlVal
Direct close
1=Close
2.5.6
LD0.LDEV1 Protection relay's warm reset (1)
Table 186:
LD0.LDEV1 Protection relay's warm reset (1)
0xA
CS
IEC 61850 name
SA name
Description
Values
LD0.LDEV1
2080
3.00
.WrmStrCmd.Oper.ctlVal
Warm reboot of protection relay
1=Reboot
2.5.7
LD0.SPCGAPC1 Generic control point (16 pcs) (1) – SPC-1
The binary outputs can be configured either as pulse- or persistent-type outputs. Pulse-
type outputs are triggered with the write value "1". Persistent-type outputs can be written
with both values "1" and "0". The setting mode "toggled" for local operation corresponds
to "persistent" for remote operation.
1MAC252756-MB B
Section 2
Modbus data mappings
REM615 ANSI
103
Point List Manual