![ABB Relion 615 series Скачать руководство пользователя страница 64](http://html1.mh-extra.com/html/abb/relion-615-series/relion-615-series_modbus-point-list-manual_3381023064.webp)
BitA
RegA
IEC 61850 name
SA name
Description
Values
.mcd
.ChgFlg.stVal
Configuration changed
1=Changed
.mcd
.FacSet.stVal
Factory settings in use
1=In use
.mcd
LD0.GNRLLTMS1
.TmChSt1.stVal
Time synch. status
0/1=Down/Up
.mcd
LD0.SCHLCCH1
.ChLiv.stVal
CH1LIV
Ethernet channel 1 live
1=Live
.mcd
LD0.SCHLCCH2
.ChLiv.stVal
CH2LIV
Ethernet channel 2 live
1=Live
.mcd
LD0.SCHLCCH3
.ChLiv.stVal
CH3LIV
Ethernet channel 3 live
1=Live
.mcd
2.3.2.3
LD0.DIAGLCCH1 Ethernet supervision (1)
Table 94:
LD0.DIAGLCCH1 Ethernet supervision (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.DIAGLCCH1
.ChLiv.stVal
CHLIV
Ethernet channel live
1=Live
.mcd
.RedChLiv.stVal
REDCHLIV
Red. Ethernet channel live
1=Live
.mcd
2.3.2.4
LD0.IL1TCTR1 Three-phase CT supervision (1)
Table 95:
LD0.IL1TCTR1 Three-phase CT supervision (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.IL1TCTR1
.Alm.stVal
ALARM
Alarm
1=Alarm
.mcd
.Wrn.stVal
WARNING
Warning
1=Warning
.mcd
Section 2
1MAC252756-MB B
Modbus data mappings
58
REM615 ANSI
Point List Manual
Содержание Relion 615 series
Страница 1: ...RELION 615 SERIES Motor Protection and Control REM615 ANSI Modbus Point List Manual...
Страница 2: ......
Страница 14: ...8...
Страница 114: ...108...