menu in PCM600. The user needs to be authorized before using the tool. User
credentials are asked if the default administrator password has been changed.
Administrator or engineer credentials are needed for authorization.
3.6.1
Prerequisites for local and remote updates
Local update
•
Use of the front port is recommended when updating locally. Remove the IED
from the network especially with redundant network topologies (HSR/PRP).
Remote update
•
Communication is recommended to be secured either by setting up a VPN
connection or enabling secure communication in the IED via LHMI
(
Configuration/Authorization/Remote Update
) while updating remotely.
•
Remote update can be enabled in the IED either via the LHMI (
Configuration/
Authorization/Security/Remote Update
) or by an administrator in the
Parameter Setting tool in PCM600 (
IED Configuration/Configuration/
Authorization/Remote Update
to be able to update remotely. If the IED is in
local control mode, remote update proceeds only after a confirmation is received
from the user.
•
Remote update has to be disabled manually after the update, if wanted.
•
Remote update only works when the IED is connected from the rear port with a
custom IP address.
3.6.2
Updating firmware or language
1.
Select the update mode.
•
Firmware
•
Language
2.
Select the update package and click
Next
.
Section 3
1MRS241255 B
PCM600 tool
30
611 series
Engineering Manual