Entering settings
Chapter 9
Establishing connection and
verifying the SPA/IEC-
communication
Procedure
1.
Set the operation of the rear SPA/IEC port to “IEC”.
The operation of the rear SPA/IEC port can be found on the local
HMI at:
Configuration/TerminalCom/SPA-IECPort
Now the SPA/IEC port operates as an IEC port.
2.
Set the slave number and baud rate for the rear IEC port
The slave number and baud rate can be found on the local HMI at:
Configuration/TerminalCom/IECCom/Communication
Set the same slave number and baud rate as set in the IEC master
system for the terminal.
3.
Set the main function type of the terminal.
The main function type can be found on the local HMI at:
Configuration/TerminalCom/IECCom/FunctionType
The main function type can be set to values from 1 to 255 accord-
ing to the standard. The value zero is default and corresponds to
not used. Examples of values that can be used are:
Table 2: Main function type examples
If the setting “OpFnType” is set to “ON” then the set value for
function type will be used for all event blocks and the disturbance
recorder, otherwise the setting on each event block and the distur-
bance recorder will decide the function type of that function block.
Value
Function type according to IEC 60870-5-103
128
Distance protection
160
Overcurrent protection
192
Line differential protection
Содержание REL 505-C1 2.3 Series
Страница 16: ...10 Note signs Chapter 2 Safety information ...
Страница 40: ...34 Checking the binary I O circuits Chapter 6 Checking the external circuitry ...
Страница 110: ...104 Two step time delayed phase overcurrent protection TOC2 Chapter 10 Verifying settings by secondary injection ...
Страница 114: ...108 Testing the interaction of the distance protection Chapter 11 Verifying the internal configuration ...