37
Energising the terminal
Chapter 7
Energising the terminal
2
Energising the terminal
When the terminal is energised the window on the local HMI remains dark. After 10
seconds the green LED starts flashing and after approximately 30 seconds the window
lights up. After another 10 seconds the window displays ‘Terminal Startup’ and after
about 30 seconds the main menu is displayed. The upper row should indicate ‘Ready’.
A steady green light indicates a successful startup.
If the upper row in the window indicates ‘Fail’ instead of ‘Ready’ and the green LED
is flashing an internal failure in the terminal has been detected. See the self supervision
function in this chapter to investigate the fault.
After startup the appearance of the local HMI should be as shown in figure 6.
Figure 6: Example of the local HMI for, in this example, REL 531.
en00000422.vsd
E
C
Ready
REL 531 Ver 2.3
C=Quit
E=Enter menu
Start
Trip
Push buttons
green yellow red
LEDs
Liquid Crystal Display
four rows
16 characters/row
Optical connector
for local PC
Содержание REL 505-C1 2.3 Series
Страница 16: ...10 Note signs Chapter 2 Safety information ...
Страница 40: ...34 Checking the binary I O circuits Chapter 6 Checking the external circuitry ...
Страница 110: ...104 Two step time delayed phase overcurrent protection TOC2 Chapter 10 Verifying settings by secondary injection ...
Страница 114: ...108 Testing the interaction of the distance protection Chapter 11 Verifying the internal configuration ...