Checking the self supervision signals
Chapter 7
Energising the terminal
3
Checking the self supervision signals
3.1
Reconfiguring the terminal
I/O modules configured as logical I/O modules (BIM, BOM, IOM, DCM, IOPSM or
MIM) are supervised. Not configured I/O modules are not supervised.
Each logical I/O module has an error flag that is set if anything is wrong with any signal
or the whole module. The error flag is also set when there is no physical I/O module of
the correct type present in the connected slot.
Procedure
1.
Browse to the ‘Reconfigure’ menu.
The Reconfigure menu is located in the local HMI under:
Configuration/I/O-modules/Reconfigure
2.
Select ‘Yes’ and press ‘E’.
3.2
Setting the terminal time
This procedure describes how to set the terminal time.
1.
Display the set time dialog.
Navigate the menus to:
Settings/Time
Press the E button to enter the dialog.
2.
Set the date and time.
Use the Left and Right arrow buttons to move between the time
and date values (year, month, day, hours, minutes and seconds).
Use the Up and Down arrow buttons to change the value.
3.
Confirm the setting.
Press the E button to set the calendar and clock to the new values.
Содержание REL 505-C1 2.3 Series
Страница 16: ...10 Note signs Chapter 2 Safety information ...
Страница 40: ...34 Checking the binary I O circuits Chapter 6 Checking the external circuitry ...
Страница 110: ...104 Two step time delayed phase overcurrent protection TOC2 Chapter 10 Verifying settings by secondary injection ...
Страница 114: ...108 Testing the interaction of the distance protection Chapter 11 Verifying the internal configuration ...